How our tanks are built
Fibreglass, steel and Glasteel II construction, double wall containment and fire protection, explained.
Get a price for your tank
Tell us what you need to store and how much. Our sales engineers in Malaysia reply with a recommendation and a quote.
Fibreglass (FRP) with integral ribs
AllTank FRP tanks are made from engineered resin and glass. Ribs and shell are the same material and are made at the same time.
Corrosion free
Resin and glass do not corrode, so there is no cathodic protection to buy or maintain.
Strength from ribs
Like the fluting in corrugated board, the ribs add strength.
Light to handle
No heavy cranes on site, which cuts installation cost.

Glasteel II: steel inside, fibreglass outside
A steel primary tank carries the load and suits a wide range of products. An FRP jacket protects it from the ground and forms the second wall.
Product compatibility
Petrol, jet fuel, diesel, ethanol, methanol and solvents such as toluene and xylene.
Tested monitoring
Ken Wilcox Associates (USA) testing shows the optional vacuum monitoring exceeds US EPA requirements.
Listed
UL 58 and UL 1746.

Double wall containment
Two walls with a free-flowing 360° interstice between them. If the inner wall leaks, the outer wall holds the product and the monitor shows it.
Interstitial monitoring
Hydrostatic or vacuum monitoring for tightness tests to US EPA criteria.
Tested twice
Pressure tested before delivery and again in the tank pit.
Sumps and covers
Flat-sided sumps and watertight covers keep spills in and water out.

Fireguard® fire protection
A steel double wall tank with 3 inches of lightweight insulation between the walls, built by AllTank under licence from the Steel Tank Institute.
4-hour rated
Built to UL 142, UL 2085 and STI F-941.
Lighter than concrete
The insulation is 75% lighter than traditional concrete insulation.
Tested
Projectile, impact and hose stream test ratings.

Which construction suits which job
| FRP double wall | Glasteel II | Fireguard® | |
|---|---|---|---|
| Installed | Underground | Underground | Aboveground |
| Primary tank | Fibreglass | Steel | Steel |
| Second wall | Fibreglass | Fibreglass jacket | Steel, insulated |
| Listed to | UL 1316 | UL 58, UL 1746 | UL 142, UL 2085, STI F-941 |
| Capacity | 5,000L to 130kL | 5,000L to 130kL | 5,000L to 130kL |
| Warranty or rating | 30-year warranty | 30-year warranty | 4-hour fire rating |